In 2010, during the 10-meter platform diving final of the Youth Olympic Games, the competition hall suddenly lost power! Diving from such heights without lighting due to a power outage can cause athletes to lose visual reference points, leading to injuries or even more tragic incidents. Fortunately, at that exact moment of power failure, young Chinese diver Qiu Bo was just taking off from the 10-meter platform and successfully completed his dive under poor lighting conditions to win the championship !

无独有偶,2007年8月16日晚上,在曼谷举行的大运会女子3米板半决赛中,突发停电事故,赛场内的照明灯光全部熄灭,导致比赛中止10分钟。
Sudden power outage during competition poses significant hazards:
Athletes are at risk. For example, in diving, gymnastics, acrobatics, etc., a sudden power outage resulting in loss of lighting can cause athletes to be injured or even put their lives at risk;
Staff and referees on the competition field are at risk. For example, with javelin or hammer throw, if lighting is lost at the moment of release, staff cannot judge the trajectory of the javelin or hammer, posing a risk of injury to staff;
If a major broadcast is interrupted due to a power outage, it will cause huge economic losses . For example, TV broadcasting fees for events like the Olympics and the FIFA World Cup can reach tens of billions of US dollars; a one-second power outage results in economic losses in the millions of dollars .
A power outage during a major competition will have significant political implications.
To this end, relevant national regulations and standards impose strict provisions and requirements on safety lighting, which must be strictly implemented!
As the name suggests, safety lighting is emergency lighting used to ensure the safety of personnel in potential danger .
JGJ 354-2014《体育建筑电气设计规范》第9.1.4条第1款规定, 观众席和运动场地安全照明的平均水平照度值不应低于20lx。
GB 55016-2021 "General Code for Building Environment" Article 3.3.11, Clause 2 stipulates that high-risk sports venues' standby lighting illuminance shall not be less than 50% of the general lighting illuminance value of the venue. The same code, Article 3.3.12, Clause 2 further stipulates that the safety lighting horizontal illuminance value of large event venues and spectator seating areas shall not be less than 20lx.
Especially GB 55016 is a mandatory national standard for engineering construction; it must be enforced strictly!